Carrier Access Network Device Axxius 800 Bedienungsanleitung Seite 512

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 568
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 511
C-2 Axxius 800 - Release 2.2
Loopback Tests
Alarms
Alarms
Test Alarm
The Axxius 800 alarm functions can be manually tested using the following command
for setting critical, major and minor alarms. Turning alarms on or off will produce
alarm messages and log entries stating the alarm event was manually set/cleared by the
user.
Syntax:
set alarms {critical|major|minor} {off|on}
Identify Alarm
Alarm indicators
l LEDs - When an Alarm is triggered, the LED will display a red/yellow
indicator light, which will stay on until the Alarm is cleared. The following
is the LED information for the Control Panel Interface card. For LED
information for a specific service card see the chapter for that card
.
LED State Description
CRITICAL Off No critical alarms present
Red Critical alarms present
MAJOR Off No major alarms present
Red Major alarm present
MINOR Off No minor alarms present
Red Minor alarms present
ACO Off Normal mode. No alarms are being
suppressed.
Red Alarm cutoff active. One or more active
alarms suppressed.
Seitenansicht 511
1 2 ... 507 508 509 510 511 512 513 514 515 516 517 ... 567 568

Kommentare zu diesen Handbüchern

Keine Kommentare